Gmr32b Phase Controller Manual 2021 -

| Flashes | Error | Solution | |---------|-------|----------| | 1 | Heatsink over-temperature (>95°C) | Reduce load, improve cooling, check fan. | | 2 | Line frequency out of range (<45 Hz or >65 Hz) | Check generator or UPS output. | | 3 | Phase loss (three-phase model) | Inspect incoming fuses, contactors, wiring. | | 4 | External semiconductor fuse blown | Replace with exact type – do not upsize. | | 5 | Control signal loss (<2 mA or <0.5 V) | Check transmitter, loop wiring, or potentiometer. | | 6 | Internal SCR short detected | Power off – replace controller (SCR failure). |